Figure 57 – Checking that the power consumption is above 200W
11.
Supply DC power to the inverter by correctly switching on the batteries.
12.
Supply AC power through the dedicated protection switch of the storage inverter. If there is more than one
switch protecting the inverter (e.g. a circuit breaker and differential switch), they must all be set to ON to
allow the inverter to be connected to the grid.
Figure 58 – Example of AC switch protecting the inverter
The following parameters must be configured before the 1PH HYD3000-HYD6000-ZP1 inverter starts working.
Parameter
Comment
1.Menu language selection
Default English
2.Set and confirm system time
If the collector or mobile APP is connected to the monitoring
system, the time has been calibrated to the local time
*3.Safety parameter import
USB import: you need to find the safety parameters file (named by
the corresponding safety country) on the website, download to the
USB, import
4.Setting the input channel
The default order: BAT1, BAT2, PV1, PV2)
5. Setup is complete