User’s Manual 1PH HYD3000-HYD6000-ZP1
Rev. 1.0 01/09/2023
Identification: MD-AL-GI-00
Rev. 1.1 of 27/01/2023 - Application: GID
128/193
ID No.
Name
Solution
ID001
The grid voltage is too high
If the alarm occurs occasionally, the possible
cause is that the electric grid is abnormal
occasionally. Inverter will automatically return to
normal operating status when the electric grid’s
back to normal.
If the alarm occurs frequently, check whether the
grid voltage/frequency is within the acceptable
range. If yes, please check the AC circuit breaker
and AC wiring of the inverter.
If the grid voltage/frequency is NOT within the
acceptable range and AC wiring is correct, but the
alarm occurs repeatedly, contact ZCS technical
support to change the grid over-voltage, under-
voltage, over-frequency, under-frequency
protection points after obtaining approval from
the local electrical grid operator.
ID002
The grid voltage is too low
ID003
The grid frequency is too high
ID004
The grid frequency is too low
ID005
Charge Leakage Fault
Internal faults of inverter, switch OFF inverter,
wait for 5 minutes, then switch ON inverter.
Check whether the problem is solved.
If not, please contact ZCS technical support.
ID006
OVRT function is faulty
ID007
LVRT function is faulty
ID008
Island protection error
ID009
Transient overvoltage of grid voltage 1
ID010
Transient overvoltage of grid voltage 2
ID012
Inverter voltage error
ID017
Power grid current sampling error
ID018
Wrong sampling of dc component of grid
current
ID019
Power grid voltage sampling error (DC)
ID020
Power grid voltage sampling error (AC)
ID022
Leakage current sampling error(AC)
ID024
Input current sampling error
ID025
DCI sampling error(AC)