User’s Manual 1PH HYD3000-HYD6000-ZP1
Rev. 1.0 01/09/2023
Identification: MD-AL-GI-00
Rev. 1.1 of 27/01/2023 - Application: GID
122/193
1PH HYD3000-HYD6000-ZP1 inverters offer software upgrade via USB flash drive to maximize inverter
performance and avoid inverter operation error caused by software bugs.
Upgrade file folder name is firmware. The three upgrade file names are HYD-EP_ARM.bin, HYD-EP_DSPM.bin,
HYD-EP_DSPS.bin.
Step 1:
Insert the USB flash drive into the compute.
Step 2:
https:///www.zcsazzurro.com/it/
you will find the latest version of the software to
carry out the update.. After user receive the file, please decompressing file and cover the original file in USB
flash drive.
Step 3:
Insert the USB flash drive into the USB/Wifi interface.
Step 4:
Then turn on DC switch.
Step 5:
6.Software Update
OK Input password
OK
Input 0715
Start Update
Updating DSP1
Updating DSP2
Updating ARM
Step 6:
If the following errors occur, please upgrade again. If this continues many times, contact technical
support for help.
USB Fault
MDSP File Error
SDSP File Error
ARM File Error
Update DSP1 Fail
Update DSP2 Fail
Update ARM Fail
Step 7:
After the update is completed,turn off the DC breaker, wait for the LCD screen extinguish, then restore
the WiFi connection and then turn on the DC breaker and AC breaker again,the inverter will enters the running
state. User can check the current software version in Systemlnfo>>SoftVersion.