User’s Manual 1PH HYD3000-HYD6000-ZP1
Rev. 1.0 01/09/2023
Identification: MD-AL-GI-00
Rev. 1.1 of 27/01/2023 - Application: GID
111/193
2)
STD self-test
Select “2. STD self-test,”
then press “OK” to start
the STD self-test. The
test procedure is the
same as the Fast Self-
Test, but much longer.
3)
PF Time Setting
Select “3. PF Time Setting”, then press “OK”. The following will appear on the screen:
Set:
*.
*** s
Press “Up” or “Down” to change the first digit, press “OK” to move to the next digit. After changing all the digits,
press “OK”.
4)
QV Time Setting
Select “4. QV Time Setting”, then press “OK”. The following will appear on the screen:
Set: ** s
Press “Up” or “Down” to change the first digit, press “OK” to move to the next digit. After changing all the digits,
press “OK”.
5)
Control 81.S1
Select “5. Control 81.S1” and press “OK.” Press “Up” or “Down” to “Enable 81.S1” or “Disable 81.S1”, press “OK.”
Test 81<S2 OK!
↓
Press “OK”
OK self-test!
↓
Press “Down”
59.S1 threshold 253V 900ms
↓
Press “Down”
59.S1: 228V 902ms
↓
Press “Down”
59.S2 threshold 264.5V 200ms
↓
Press “Down”
59.S2: 229V 204ms
↓
Press “Down”
27.S1 threshold 195.5V 400ms