Table 13: Display only fields
Field/LED name
Description
Leaving Chilled Liquid
Temperature Setpoints –
Setpoint
Displays the present setpoint to which the chiller is operating,
whether controlled locally or remotely.
Leaving Chilled Liquid
Temperature Setpoints –
Shutdown
Displays the Leaving Chilled Liquid Temperature at which the chiller
will shutdown on Leaving Chilled Liquid – Low Temperature. This
temperature is entered as an offset with the Leaving Chilled Liquid
Temperature Cycling Offset – Shutdown Setpoint below. Although
the offset setpoint is changed manually, the offset being used
can change automatically to prevent the Leaving Chilled Liquid
Temperature from going below the minimum allowed value: 36°F
(water), 34°F (water with smart freeze enabled) or 6°F (brine). The
offset being used is displayed as Effective Offset.
Leaving Chilled Liquid
Temperature Setpoints –
Restart
Displays the Leaving Chilled Liquid Temperature at which the chiller
will restart after it has shutdown on LEAVING CHILLED LIQUID –
LOW TEMPERATURE cycling shutdown. This temperature is set as an
offset using the Leaving Chilled Liquid Temperature Cycling Offset –
Restart Setpoint, displayed as OFFSET adjacent to this value.
Table 14: Programmable
Button
Access level Description
Smart Freeze
(Off / On)
Service
This value is only available if the chiller is not in Brine mode. It
allows the user to enable the Smart Freeze Point Operation which
allows the chiller to run closer to the freeze point without shutting
down.
Brine Low
Evaporator
Cutout
Service
This value is only available in Brine mode. It allows the user to
specify the Evaporator Pressure at which a safety shutdown is
initiated.
Refrigerant
(Enabled /
Disabled)
Service
When an Evaporator Refrigerant Sensor has been installed it must
be enabled via this toggle before the system will utilize the new,
enhanced resolution input.
Local Leaving
Chilled Liquid
Temperature
– Range
Operator
This is the range over which an analog (0 to 20mA, 4 to 20mA, 0 to
10VDC or 2 to 10VDC) in Analog Remote mode or a digital signal
(PWM) in Digital Remote mode can reset the Leaving Chilled Liquid
Temperature Setpoint above the operator programmed BASE
Setpoint. Programmable as 10, 20, 30 or 40°F. It is added to the BASE
value to create a range over which the remote device can reset the
setpoint. For example, if this setpoint is programmed for 10°F and
the operator programmed value is 45°F, then the remote device can
set the Leaving Chilled Liquid Temperature Setpoint over the range
of 45.0° to 55.0°F.
31
YK-EP Style B Centrifugal Chiller
Содержание 160.87-OM1
Страница 2: ...2 YK EP Style B Centrifugal Chiller ...
Страница 6: ...6 YK EP Style B Centrifugal Chiller ...
Страница 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Страница 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Страница 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Страница 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Страница 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Страница 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Страница 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Страница 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Страница 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Страница 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...
Страница 260: ...Figure 87 Microboard 031 03630 007 Figure 88 Program card 031 03601 002 YK EP Style B Centrifugal Chiller 260 ...