background image

Process Fluid Chiller Designed for CTI PETNet Cyclotron          1

Keeping Business in Business

Process Fluid Chiller

Designed for CTI PETNet Cyclotron

• Dedicated, equipment-matched cooling supplies the proper temperature and water flow year round.
• Factory-tested, piped, wired and charged for hassle-free startup and operation.
• Clean, non-ferrous cooling loop, required for sensitive medical equipment.
• Local service and parts for quick and knowledgeable maintenance and service.
• Optional switch-over to alternate water source provides redundant, continuous operation.
• Optional remote monitoring systems keep you informed of chiller operation.
• UL/CSA listing on standard models.
• ISO 9001 certified company.

PETNet Cyclotron Specifications

Fluid Specified

Water

Heat Dissipation—BTUH (kW)

60,000 (17.6)

Fluid Temperature Range—°F (°C)

40-50 (4.4-10)

Fluid Flow Rate—GPM (l/m)

10 (38)

Fluid Pressure Drop—PSI (kPa)

5 (34)

Note:

 Performance is based on 95°F condenser ambient.

Process Fluid Chiller Specifications

Model Number

PS096A

PS096A

Fluid Circulated

Ethylene Glycol

Propylene Glycol

Net Cooling Capacity—BTUH (kW)

72,400 (21.2)

68,200 (20)

Leaving Fluid Temperature—°F (°C)

45 (7.2)

45 (7.2)

Fluid Flow Rate—GPM (l/m)

10 (38)

10 (38)

PETNet Cyclotron Pressure Drop—PSI (kPa)

5 (34)

5 (34)

Chiller Pressure Drop—PSI (kPa)

6.6 (45)

8.0 (54.5)

Pump Total Head—PSI (kPa)

65 (448)

65 (448)

Head Available for Piping Circuit—PSI (kPa)

53.4 (369)

52.0 (360)

Pump HP (kW)

3 (2.2)

3 (2.2)

Based on Siemens specification dated 07/97

Отзывы: