![York 160.87-OM1 Скачать руководство пользователя страница 201](http://html.mh-extra.com/html/york/160-87-om1/160-87-om1_operation-and-maintenance-manual_912610201.webp)
LCSSS – Phase Locked Loop
The Liquid Cooled Solid State Starter Logic/Trigger Board phase locked loop circuit was not able to
maintain lock with phase A of the power line. This could be caused by a power line anomaly such
as sag or jitter. A power line frequency jitter of up to 3 Hz/second can be tolerated. The chiller will
automatically restart when lock has resumed.
LCSSS – Low Supply Line Voltage
The Liquid Cooled Solid State Starter Logic/Trigger Board has detected that the compressor motor
AC Power Line Voltage, in any phase, decreased below the low line voltage threshold continuously
for 20 seconds. The chiller will automatically restart when the voltage in all phases returns to the
restart level. The thresholds are as follows:
Table 203: Voltage thresholds
Supply voltage
range (Volts)
Shutdown (Volts)
Restart (Volts)
Disabled
None
N/A
200-208
160
174
220-240
185
200
380
305
331
400
320
349
415
335
362
440-480
370
400
550-600
460
502
LCSSS – High Supply Line Voltage
The Liquid Cooled Solid State Starter Logic/Trigger Board has detected that the compressor motor
AC Power Line Voltage, in any phase, exceeded the high line voltage threshold continuously for 20
seconds. The chiller will automatically restart when the voltage in all phases returns to the restart
level. The thresholds are as follows:
Table 204: Voltage thresholds
Supply voltage
range (Volts)
Shutdown (Volts)
Restart (Volts)
Disabled
None
N/A
200-208
227
226
220-240
262
261
380
415
414
400
436
435
415
454
453
440-480
524
523
550-600
655
654
LCSSS – Logic Board Processor
Communication between the V25 Microprocessor and Digital Signal Processor (DSP) on the Liquid
Cooled Solid State Starter Logic/Trigger Board has been interrupted. The chiller will automatically
restart when communications are restored.
201
YK-EP Style B Centrifugal Chiller
Содержание 160.87-OM1
Страница 2: ...2 YK EP Style B Centrifugal Chiller ...
Страница 6: ...6 YK EP Style B Centrifugal Chiller ...
Страница 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Страница 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Страница 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Страница 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Страница 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Страница 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Страница 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Страница 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Страница 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Страница 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...
Страница 260: ...Figure 87 Microboard 031 03630 007 Figure 88 Program card 031 03601 002 YK EP Style B Centrifugal Chiller 260 ...