Warning – Evaporator – Low Pressure Limit
The Evaporator Pressure has decreased to the Warning threshold. This threshold is fixed in Water
cooling applications. In Brine cooling applications, the threshold is a fixed amount above the
programmable safety shutdown threshold. The Safety threshold in Brine applications is determined
by the Brine solution and is determined by the YORK Factory. While this condition is in effect, the
Pre-Rotation Vanes are inhibited from further opening. This message automatically clears and the
Vanes are permitted to open when the Evaporator Pressure increases to the reset value.
Table 198: Warning and reset thresholds
Warning threshold (PSIG)
Reset threshold (PSIG)
Water
Brine
Water
Brine
R22
56.2
+1.9 more than Safety Setpoint
57.5
+3.2 more than Safety Setpoint
R134a
27.0
+2.0 >Safety Setpoint
28.0
+3.0>Safety Setpoint
Warning – Vanes Uncalibrated – Fixed Speed
The Compressor Motor Variable Speed Drive (VSD) is operating Fixed Speed (full speed) mode
because the Pre-Rotation Vanes position potentiometer calibration has not been performed.
Warning – Harmonic Filter – Operation Inhibited
The Compressor Motor Variable Speed Drive (VSD) Harmonic Filter has been inhibited. Refer to
Variable Speed Drive – Service Instructions (Form 160.00-M1)
. Harmonic Filter operation should not be
altered by anyone other than a qualified Service Technician.
Warning – Harmonic Filter – Data Loss
Communications between the Harmonic Filter Logic Board and the Compressor Motor Variable
Speed Drive VSD Logic Board or the Adaptive Capacity Control Board is not occurring. While this
condition exists, all filter related parameters are displayed as X’s. This message automatically clears
when communications are restored.
Warning – Harmonic Filter – Input Frequency Range
The power line frequency detected by the Compressor Motor Variable Speed Drive (VSD) Harmonic
Filter is outside the range of 58 to 62 Hz (60 Hz), or 49 to 51 Hz (50 Hz). While this condition exists,
all filter related parameters are displayed as X’s. This message automatically clears when the line
frequency is within range.
Warning – Harmonic Filter – Not Running
This warning is set when all of the following are true for 20 continuous seconds:
•
Chiller is running
•
Filter is enabled
•
Filter present status is true
•
Run Time greater than 20 seconds
•
Filter operating mode is stopped
This warning is released when the chiller is stopped, but will be displayed until manually cleared
using the WARNING RESET key when logged in at OPERATOR (or higher) access level.
Warning – Vanes Uncalibrated
The Hot Gas Bypass feature is enabled, but the Pre-Rotation Vanes calibration procedure has not
yet been performed.
193
YK-EP Style B Centrifugal Chiller
Содержание 160.87-OM1
Страница 2: ...2 YK EP Style B Centrifugal Chiller ...
Страница 6: ...6 YK EP Style B Centrifugal Chiller ...
Страница 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Страница 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Страница 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Страница 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Страница 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Страница 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Страница 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Страница 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Страница 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Страница 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...
Страница 260: ...Figure 87 Microboard 031 03630 007 Figure 88 Program card 031 03601 002 YK EP Style B Centrifugal Chiller 260 ...