Table 48: Programmable
Button
Access level Description
Surge
Sensitivity
Service
Allows the user to define the surge detection sensitivity of the
Surge Protection feature. The Surge Sensitivity Setpoint on the
ACC DETAILS Screen sets the sensitivity of the ACC Surge Detection
feature that is employed for ACC Surge Detection. Selectable over
the range of 0.3 to 1.3; default 0.3. The smaller the number, the
greater the sensitivity.
Note:
*
When an Excess Surge situation is detected, the action depends upon the following:
•
If both the Shutdown and Extended Run Setpoints are Disabled, the chiller will continue
to run, displaying the message WARNING – EXCESS SURGE DETECTED. Refer to Hot
Gas Bypass and Variable Speed Drive exceptions. See
Shutdown (Enabled/Disabled)
and
Extended Run (Enabled/Disabled)
in Table 48.
•
If the Shutdown Setpoint is Enabled and the Extended Run Setpoint is Disabled, the
chiller will perform a safety shutdown and display Surge Protection – Excess Surge. Refer
to Hot Gas Bypass and Variable Speed Drive exceptions. See
Shutdown (Enabled/ Disabled)
and
Extended Run (Enabled/Disabled)
•
If the Shutdown Setpoint is Disabled and the Extended Run Setpoint is Enabled, the Pre-
Rotation Vanes are driven closed for 10 minutes and WARNING – SURGE PROTECTION
– EXCESS SURGE LIMIT is displayed. When the 10 minutes have elapsed, if the Surge
Window Count is less than or equal to the Count Limit, this message and load inhibit
are automatically cleared. Alternating with this message is WARNING – EXCESS SURGE
DETECTED that continues after the 10 minute period has elapsed until manually cleared
with the WARNING RESET key. Refer to Hot Gas Bypass and Variable Speed Drive
exceptions. See
Shutdown (Enabled/Disabled)
and
Extended Run (Enabled/Disabled)
•
If both the Shutdown and Extended Run Setpoint are Enabled, the 10 minute Extended
Run mode is invoked as described above. However, if the Surge Window Count exceeds
the Count Limit at the completion of the 10 minute Extended Run period, a safety
shutdown is performed and Surge Protection – Excess Surge is displayed. Refer to Hot
Gas Bypass and Variable Speed Drive exceptions. See
Shutdown (Enabled/Disabled)
and
Extended Run (Enabled/Disabled)
Table 49: Navigation
Button
Access level Description
Home
View
Returns user to HOME Screen.
Compressor View
Returns user to COMPRESSOR Screen.
63
YK-EP Style B Centrifugal Chiller
Содержание 160.87-OM1
Страница 2: ...2 YK EP Style B Centrifugal Chiller ...
Страница 6: ...6 YK EP Style B Centrifugal Chiller ...
Страница 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Страница 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Страница 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Страница 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Страница 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Страница 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Страница 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Страница 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Страница 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Страница 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...
Страница 260: ...Figure 87 Microboard 031 03630 007 Figure 88 Program card 031 03601 002 YK EP Style B Centrifugal Chiller 260 ...