Advanced trend setup screen
Figure 67: Advanced trend setup screen
The desired data collection start/stop triggers are setup on this screen. The trend data collection
can be set to start or stop based upon the status of up to two selected triggers.
The triggers can consist of digital events or analog parameters compared to thresholds. The
triggers can be used individually or in combination. The digital and analog parameters are selected
from the COMMON SLOTS Screen (or Master Slot Numbers List in this manual).
The parameter selected as the Primary Trigger is compared to a value selected as the Primary Test,
using the Primary Operator as a comparator. If it is evaluated as true, then the data collection is
started or stopped (after any selected trigger delay) per the selected Trigger Action.
A Secondary Trigger can be evaluated with the Primary Trigger to start/stop data collection. The
Primary to Secondary Operator is used to define the trigger combinations required to be true to
start/stop data collection. The Secondary Trigger is setup and evaluated the same as the Primary
Trigger.
Entry fields are as follows:
1. Primary Trigger
a. Primary Operator
b. Primary Test
2. Primary to Secondary Operator
3. Secondary Trigger
a. Secondary Operator
b. Secondary Test
181
YK-EP Style B Centrifugal Chiller
Содержание 160.87-OM1
Страница 2: ...2 YK EP Style B Centrifugal Chiller ...
Страница 6: ...6 YK EP Style B Centrifugal Chiller ...
Страница 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Страница 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Страница 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Страница 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Страница 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Страница 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Страница 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Страница 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Страница 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Страница 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...
Страница 260: ...Figure 87 Microboard 031 03630 007 Figure 88 Program card 031 03601 002 YK EP Style B Centrifugal Chiller 260 ...