Table 107: Motor rated voltage (V)*
Model in HP
2300 V
3300 V
4160 V
900
202 A
141 A
112 A
1000
224 A
156 A
125 A
1250
280 A
195 A
155 A
1500
336 A
235 A
186 A
1750
392 A
274 A
217 A
2000
438 A
312 A
248 A
2250
494 A
345 A
274 A
2500
561 A
391 A
310 A
Note:
*Max. Job/Rated 100% FLA (A) (Programmed Drive Current)
Table 108: Programmable
Button
Access level Description
Local Motor
Current Limit Operator
Allows the user to specify the maximum allowed motor current (as
a percentage of FLA). When the motor current reaches this value,
the Pre-Rotation Vanes will not be permitted to open further. If the
motor current rises above this value, the Pre-Rotation Vanes will
close to reduce the current to this value.
Pulldown
Demand
Limit
Operator
Allows the user to specify the current limit value (as percentage
of FLA) to which the chiller will be limited during the specified
pulldown limit time. This value will override the Motor Current
Limit value during this time period. This function is used to provide
energy savings following chiller start-up.
Pulldown
Demand
Time
Operator
Allows the user to set a period of time for which the pulldown
demand limit will be in effect after the chiller starts.
Full Load
Amps
Service
Defines the maximum amps at which the motor can operate this
value is viewable when logged in at VIEW or OPERATOR level.
The maximum programmable value of this setpoint is equal to
Programmed Drive Current value received from the MVVSD.
KWH Reset
Service
Allows the user to reset the cumulative Kilowatt hours to zero.
Table 109: Navigation
Button
Access level Description
Home
View
Returns user to HOME Screen.
ACC Details
Service
Moves to a subscreen which provides more information about the
Adaptive Capacity Control.
Motor Lube
–
Moves to a subscreen allowing operator acknowledgement of the
compressor motor lubrication and viewing of the compressor motor
lubrication parameters.
Motor Details Service
Moves to a subscreen that provides information and setpoints
pertinent to the Motor Monitoring feature.
YK-EP Style B Centrifugal Chiller
110
Содержание 160.87-OM1
Страница 2: ...2 YK EP Style B Centrifugal Chiller ...
Страница 6: ...6 YK EP Style B Centrifugal Chiller ...
Страница 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Страница 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Страница 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Страница 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Страница 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Страница 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Страница 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Страница 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Страница 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Страница 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...
Страница 260: ...Figure 87 Microboard 031 03630 007 Figure 88 Program card 031 03601 002 YK EP Style B Centrifugal Chiller 260 ...