Страница 1: ...REMOVAL PROCEDURE S E R V I C E M A N U A L Outdoor Unit Non Inverter Multi Type 5 6 kW Class Si11 990...

Страница 2: ...Service Manual Removal Procedure Outdoor Unit zCooling Only 2M56GV1G...

Страница 3: ...Si11 990 Removal Procedure 1 Table of Contents 1 Removal of Electrical Component ASSY 2 2 Removal of Solenoid Valve Coil ASSY 12 3 Removal of Fan Motor 13 4 Removal of Sound Blankets Compressor 14...

Страница 4: ...ing off all power supplies before disassembling work Step Procedure Points 1 Removal of the outer panels 1 External appearance 2 Remove the 4 screws of the top panel and the 6 screws of the front pane...

Страница 5: ...Removal Procedure 3 2 Removal of the electrical component ASSY 1 Internal appearance 2 Release the outdoor temperature thermistor from the hook Step Procedure Points Solenoid valve Service port R10767...

Страница 6: ...outdoor temperature thermistor S7 from the PCB 5 Unhook the sealing material of the fan motor lead wire from the hook The sealing material should be mounted as below 6 Disconnect the relay connector...

Страница 7: ...the clamp 8 Disconnect the 2 lower harness of the compressor motor capacitor 9 Cut the 2 clamps 10 Disconnect the harness 6 from the magnetic contactor Step Procedure Points R10773 Compressor motor ca...

Страница 8: ...SA white SB red 12 Remove the fixing screw of the electrical component ASSY on the right side 13 Remove the fixing screw of the electrical component ASSY in the front side 14 Lift up and remove the el...

Страница 9: ...ransformer S4 S5 indoor unit room A room B S6 fan motor S8 rectifier unit 1 Disconnect the connectors S6 S3 S2 S8 S5 S4 S1 2 Release the 6 PCB spacer 3 Lift up and remove the PCB from the electrical c...

Страница 10: ...sconnect the harness A1 A2 from the magnetic contactor 2 Remove the screw Remove the rectifier unit 5 Removal of the compressor motor capacitor 1 Disconnect the harness from the compressor motor capac...

Страница 11: ...from the band 3 Remove the compressor motor capacitor 6 Removal of the fan motor capacitor 1 Disconnect the 3 connectors 1 2 4 from the fan motor capacitor 2 Remove the screw Remove the fan motor capa...

Страница 12: ...the fuse 1 Open the fuse cover 2 Take the fuse out from the fuse cover 8 Removal of the surge absorber 1 Disconnect the harness from the surge absorber 2 Remove the screw Remove the surge absorber St...

Страница 13: ...val of Electrical Component ASSY Removal Procedure 11 9 Removal of the high frequency transformer 1 Remove the 2 screws Remove the high frequency transformer Step Procedure Points High frequency trans...

Страница 14: ...ASSY Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Cut the clamp 2 Remove the screws from the solenoid va...

Страница 15: ...fore disassembling work Step Procedure Points 1 Removal of the outdoor fan Wrench size 10mm 1 Unscrew the nut M6 and remove the outdoor fan 2 Removal of the fan motor 1 Remove the 2 screws Remove the...

Страница 16: ...re disassembling work Step Procedure Points 1 Removal of the right side panel 1 Remove the 5 screws of the right side panel 2 Lift up and remove the right side panel 2 Removal of the partition plate 1...

Страница 17: ...cause the sawdust come into the circuit The brazed parts are hot after being disconnected To avoid a burn make sure that the compressor is cooled down before removing 1 Remove the flange nut and open...

Страница 18: ...Revision History Month Year Version Revised contents 02 2013 Si11 990 First edition...