16-8
IM 05P01D31-01EN
Errors during Operation (3)
The errors shown below may occur during operation.
PV display
(Operation
Display)
Setpoint display
(Operation
Display)
Status indicator
(Operation
Display)
Parameter
that
displays error
details
Error description
Cause and diagnosis
Remedy
Normal
indication
0.000 00000
(Decimal point
on the left of the
Symbol display
blinks)
–
Setup
parameter
(OP.ER)
Peer-to-peer
communication error
Peer-to-peer communication error
Check that the target devices are connected
correctly.
Recovery at normal receipt.
AT,E
Normal indication
–
Setup
parameter
(PV1.E)
Auto-tuning time-out
Auto-tuning does not end even when 24 hours
have elapsed after the start of tuning.
Check the process. Hold down any key to
erase the error indication
VAT,E
Normal indication
–
Setup
parameter
(AD2.E)
Automatic valve position
adjustment error
Fully-closed valve position is equal to or
larger than the fully-open valve position
after automatic valve position adjustment is
performed.
Check wiring and valve. Hold down any key to
erase the error indication.
Normal
indication
0.000 00000
(Decimal point
on the left of the
Symbol display
blinks)
–
Setup
parameter
(OP.ER)
Communication error
(RS-485 communication)
Framing parity error
Buffer overflow
Inter-character time-out
Checksum error (PC link communication with
checksum)
CRC check error (Modbus/RTU)
LRC check error (Modbus/ASCII)
Check the communication parameters.
Recovery at normal receipt.
Hold down any key to stop blinking.
Normal
indication
0.000 00000
(Decimal point
on the left of the
Symbol display
blinks)
–
Setup
parameter
(OP.ER)
Communication error
(coordinated operation)
Inconsistence of loop between coordinated
master and slaves
Check the communication parameters.
Recovery at normal receipt.
Change from remote to local mode to stop
blinking.
When the mode is changed from remote to local, SP
tracking does not work even if it is set to ON.
Communication from coordinated master is
interrupted for 2 seconds.
Normal
indication
0.000 00000
(Decimal point
on the left of the
Symbol display
blinks)
–
Setup
parameter
(OP.ER)
User profile error
User profile is corrupted.
Download the user profile again.
Normal
indication
Normal indication
Rightmost decimal
point on Symbol
display blinks.
Setup
parameter
(PA.ER)
Faulty FRAM
Writing (storing) data to FRAM is impossible.
Faulty. Contact us for repair.
16.1
T
roubleshooting
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...