15-1
IM 05P01D31-01EN
Power Failure Recovery Processing / Setting Power Frequency / Other S
ettings
15
15.1 Remedies if Power Failure Occurs during
Operations
Description
The operation status and remedies after a power failure differ with the length of power
failure time:
Regardless of the length of power failure time, all functions of the controller cannot be
operated for about 10 seconds after recovery. However, the case of instantaneous power
failure is excepted.
• 100–240 V AC: Instantaneous power failure of 20 ms or less
• 24 V AC/DC: Instantaneous power failure of 1 ms
A power failure is not detected. Normal operation continues.
• Power failure of about less than 5 seconds
The following shows effects caused in “settings” and “operation status.”
Alarm action
Does not continue. Alarm with stand-by function will enter stand-by status.
Alarm latch will be initialized.
Setting parameter
Set contents of each parameter are retained.
Auto-tuning
Cancelled.
Control action
Action before power failure continues.
Timer, counter (ladder
program)
Initialized.
• Power failure of about 5 seconds or more
The following shows effects caused in “settings” and “operation status.”
Alarm action
Does not continue. Alarm with stand-by function will enter stand-by status.
Alarm latch will be initialized.
Setting parameter
Set contents of each parameter are retained.
Auto-tuning
Cancelled.
Control action
Differs with setting of the parameter “R.MD” (restart mode).
R.MD setting Control action after recovery from power failure
CONT
Continues action before power failure. (Factory default)
MAN
(*)
Outputs the preset output value (PO) of the PID group
used as control output and continues action in MAN
mode.
AUTO
(*)
The control computation is executed in AUTO mode
based on the preset output value (PO) of the PID group
used as control output.
* In Heating/cooling control, starts action from 50% of control computation
output.
Timer, counter (ladder
program)
Initialized.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
R.MD
Restart mode
STD
CONT: Continue action set before
power failure.
MAN: Start from MAN.
AUTO: Start from AUTO.
SYS
Chapter 15 Power Failure Recovery Processing / Power Frequency Setting / Other Settings
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...