9-3
IM 05P01D31-01EN
Auxiliary Control Functions
9
70
ºC
/min
UPR = 140/2 = 70 (
ºC
/min)
Temperature rise time of 2 min.
SP of group 2
SP of group 1
SP of group 2= 640
ºC
SP of group 1 = 500
ºC
SP switch
Temperature
difference of 140
ºC
UPR =
=
Time (min)
Temperature difference (ºC)
= 70 (ºC/min)
2 min
140ºC
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
UPR
SP ramp-up rate
EASY
OFF, 0.0 + 1 digit to 100.0% of PV
input range span (EUS)
SPS
DNR
SP ramp-down rate
EASY
TMU
SP ramp-rate time
unit
EASY
HOUR: Ramp-up rate or ramp-
down rate per hour
MIN: Ramp-up rate or ramp-down
rate per minute