11-12
IM 05P01D31-01EN
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
AL1 to AL4
Alarm-1 to -4 type
EASY
See the table below.
ALRM
VT1 to VT4
PV velocity alarm time
setpoint 1 to 4
EASY
00.01 to 99.59
(minute.second)
Note1: The initial values of the parmeters AL1 to AL4 and VT1 to VT4 are "4". The number of alarms
can be changed using the parameter ALNO.
The following shows the example of setting PV high limit (01), With stand-by action (1),
De-energized (1), and Latch 1 action (1).
Alarm type
Symbol
Stand-by action
Energized/de-energized
Latch
Name
Latch action
(Note 1)
Energized (0) /
de-energized (1)
Stand-by action
Without (0) / with (1)
Alarm
type
Disable
- (Note 2)
- (Note 2)
- (Note 2)
00
PV high limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
01
PV low limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
02
SP high limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
03
SP low limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
04
Deviation high limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
05
Deviation low limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
06
Deviation high and low limits
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
07
Deviation within high and low
limits
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
08
Target SP high limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
09
Target SP low limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
10
Target SP deviation high limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
11
Target SP deviation low limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
12
Target SP deviation high and
low limits
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
13
Target SP deviation within
high and low limits
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
14
Control output high limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
15
Control output low limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
16
Cooling-side Control output
high limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
17
Cooling-side Control output
low limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
18
Analog input PV high limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
19
Analog input PV low limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
20
Feedback input high limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
27
Feedback input low limit
0 / 1 / 2 / 3 / 4
0 / 1
0 / 1
28
PV velocity
0 / 1 / 2 / 3 / 4
0 / 1
- (Note 2)
29
Fault diagnosis
0 / 1 / 2 / 3 / 4
0 / 1
- (Note 2)
30
FAIL
- (Note 2)
- (Note 2)
- (Note 2)
31
Note 1: 0: No latch function, 1: Latch 1, 2: Latch 2, 3: Latch 3, 4: Latch 4
Note 2: -: Alarm function doesn't work even if any value is set.
11.1 Setting Alarm Type
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...