6-19
IM 05P01D31-01EN
Monitoring and Control of Regular Operations
6
Manual PID Tuning Procedure
(1) In principle, auto-tuning must be used.
(2) Tune PID parameters in the order of P, I, and D. Adjust a numeric slowly by
observing the result, and keep notes of what the progress is.
(3) Gradually reduce P from a larger value. When the PV value begins to oscillate, stop
tuning and increase the value somewhat.
(4) Also gradually reduce I from a larger value. When the PV value begins to oscillate (with
long period), stop tuning and increase the value somewhat.
(5) Gradually increase D from a smaller value. When the PV value begins to oscillate (with
short period), stop tuning and lower the value slightly.
Reference Values for Manual Tuning of Temperature, Pressure, and Flow Rate
Setting range
(reference)
Initial value for tuning (reference)
Pressure
P
100 to 300%
200%
I
5 to 30 s
15 s
D
OFF
OFF
Flow rate
P
100 to 240%
150%
I
8 to 30 s
20 s
D
OFF
OFF
Temperature
(electric
furnace)
P
1 to 20%
5%
I
180 to 600 s
240 s
D
1/4 to 1/6 of I
60 s
6.4 Adjusting PID Manually
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...