18.2 List of Parameters
18.2.1 Operation Parameters
Operation Mode Menu (Menu: MODE)
Parameter
symbol
Name
Display
level
Setting range
Initial value
S.R
STOP/RUN switch
EASY
STOP: Stop mode
RUN: Run mode
Preset output (PO) is generated in
STOP mode.
Default: Not displayed. STOP/RUN
switch is assigned to contact input.
RUN
R.L
REMOTE/LOCAL
switch
EASY
LCL: Local mode
REM: Remote mode
(Displayed only in cases where the
communication is specified.)
LCL
AT
Auto-tuning switch
EASY
OFF: Disable
1 to 4: Perform auto-tuning. Tuning
result is stored in the specified
numbered PID.
R: Tuning result is stored in the
PID for reference deviation.
OFF
SPNO.
SP number
selection
EASY
1 to 4 (Depends on the setup
parameter SPGR. setting.)
1
PID
PID number
EASY
The PID group number being
selected is displayed.
1 to 4, R: PID group for reference
deviation
1