6-12
IM 05P01D31-01EN
Description
Auto-tuning is a function with which the controller automatically measures the process
characteristics and sets PID constants, which are control-related parameters, to optimum
values for the setpoint. Auto-tuning temporarily executes ON/OFF control, calculates
appropriate PID constants from response data obtained, and sets these constants.
CAUTION
Do not perform auto-tuning for the following processes.
Tune PID manually.
● Processes with fast response such as flow rate control and pressure control.
● Processes which do not allow the output to be turned on and off even
temporarily.
● Processes which prohibit output changes at control valves (or other actuators).
● Processes in which product quality can be adversely affected if PV values
fluctuate beyond their allowable ranges.
AT = Started
ON
OFF
Temperature
SP
Control
output
Time
ON/OFF control
PID control using PID
constants calculated from
the AT results
Auto-tuning in progress
MAN lamp blinkng
There is a hysteresis of 0.25% of the input range above and below SP.
When SP bias in auto-tuning is set
AT = Started
ON
OFF
Temperature
SP+AT.BS
SP
Control
output
Time
ON/OFF control
SP bias in auto-tuning
(negative setpoint)
PID control using PID
constants calculated from
the AT results
Auto-tuning in progress
MAN lamp blinkng
There is a hysteresis of 0.25% of the input range above and below SP.
6.3 Performing and Canceling Auto-tuning
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...