10-1
IM 05P01D31-01EN
Output
(Control
and
Retransmission)
Functions
10
10.1 Setting Control Output Type
Description
Time Proportional Relay Output / Triac Output / Time Proportional Voltage
Pulse Output
In time proportional output, the control computation result is output in the form of an
on/off signal pulse width proportional to the time. The pulse width is calculated as follows
with the cycle time (control output cycle) at 100%.
Control output pulse width = Control output (%) x Cycle time
The output type is selected as either the relay/triac output or the voltage pulse output.
100
0
0.0
50.0
100.0
ON
OFF
PV
TC
UT35A/UT32A
Heater
Tank
SSR
ON/OFF signal
pulse output
Displayed output value (%)
On-time ratio
ON
OFF
Ristricted to the range
between output high
limit and output low
limit values.
► Cycle time: 10.2 Setting Control Output Cycle Time
Current Output
In current output, the control computation result is output as a current signal. (Example of
4 to 20 mA)
20 mA
4 mA
0.0
100.0
TC
UT35A/UT32A
PV
Heater
Furnace
Displayed output value (%)
Control output
Control output
Thyristor unit
Ristricted to the range
between output high
limit and output low
limit values.
ON/OFF Output
ON/OFF control compares the SP and PV and outputs an on or off signal according to
the positive or negative deviation (PV – SP).
Chapter 10 Output (Control and Retransmission) Functions
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...