10-28
IM 05P01D31-01EN
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
RTS
Retransmission
output type of RET
EASY
OFF: Disable
PV1: PV
SP1: SP
OUT1: OUT (Valve opening: 0 to
100 % in Position proportional
control)
LPS: 15 V DC loop power supply
TSP1: Target SP
HOUT1: Heating-side OUT
COUT1: Cooling-side OUT
MV1: Position proportional output
(internal computed value)
PV: PV terminals analog input
OUT
O1RS
Retransmission
output type of OUT
current output
EASY
Parameters and Corresponding Terminals
RTS
RET/OUT2 terminal
O1RS
OUT terminal
10.15 Using 15 V DC Loop Power Supply