12-4
IM 05P01D31-01EN
Bit-0 to Bit-2 of PID Number (PN.B0 to PN.B2)
The PID number can be switched using contact input. There are two methods to specify
a PID number.
• Status switch 1 (Operation by keystroke or via communication is enabled depending
on the conditions.)
PID number
Contact status
PN.B2
PN.B1
PN.B0
1
OFF
OFF
ON
2
OFF
ON
OFF
3
OFF
ON
ON
4
ON
OFF
OFF
*1: “1” when the contact input is turned on and “0” when turned off.
*2: PID number can be switched by keystroke or via communication when all contact inputs of
PN.B0 to PN.B3 are turned off.
*3: PID number cannot be switched by keystroke or via communication when any contact input of
PN.B0 to PN.B3 is turned on.
*4: The contact input is turned off when the bit of PID number is not assigned to the contact input.
• Status switch 2 (Operation by keystroke or via communication is disabled.)
PID number
Contact status
PN.B2
PN.B1
PN.B0
1
OFF
OFF
OFF
2
OFF
OFF
ON
3
OFF
ON
OFF
4
OFF
ON
ON
*1: “1” when the contact input is turned on and “0” when turned off.
*2: Contact input is turned off when the bit of PID number is not assigned to the contact input.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
PN.BC
Bit changing method of
PID number
PRO
0: Status switch 1
1: Status switch 2
DI.NU
12.1 Setting Contact Input Function
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...