Heater Break Alarm Setting Menu (Menu: HBA)
Parameter
symbol
Name
Display
level
Setting range
Initial value
HB1.S,
HB2.S
Heater break
alarm-1, -2 function
selection
EASY
0: Heater current measurement
1: Heater break alarm (Heating-
side)
2: Cooling-side heater break alarm
1
HB1, HB2
Heater break
alarm-1, -2 current
setpoint
EASY
OFF, 0.1 to 300.0 Arms
OFF
CT1.T, CT2.T
CT1, CT2 coil
winding number
ratio
EASY
1 to 3300
800
HDN1, HDN2
Heater break
alarm-1, -2 On-
delay timer
STD
0.00 to 99.59 (minute.second)
0.00
HDF1, HDF2
Heater break
alarm-1, -2 Off-
delay timer
PRO
0.00
HB1.D,
HB2.D
Heater break
alarm-1, -2 contact
type
PRO
CLS: When the event occurs, the
contact is closed.
OPN: When the event occurs, the
contact is opened.
CLS
18.2 List of Parameters