8-20
IM 05P01D31-01EN
8.2.4 Two-position Two-level Control
Description
Two-position two-level control outputs the ON signal and OFF signal for the target
setpoint (SP) of the main setting and the sub-target setpoint (SP + SUB) of the sub-
setting.
The sub-setting is set as a deviation from the main setting.
Hysteresis can be set in the vicinity of the on/off output operating point
► Two-position two-level control: 8.1.1 Single-loop Control, Heating/cooling Control, Position
Proportional Control, and Two-position Two-level Control
Main setting=Direct and Sub-setting=Direct
OFF
ON
Output
PV
Main SP (SP)
Hysteresis (HYS)
Hysteresis (SU.HY)
Sub-SP (SP+SUB)
Main setting=Reverse and Sub-setting=Direct
OFF
ON
Output
PV
Main SP (SP)
Hysteresis (HYS)
Hysteresis (SU.HY)
Sub-SP (SP+SUB)
Main setting=Direct and Sub-setting=Reverse
OFF
ON
Output
PV
Main SP (SP)
Hysteresis (HYS)
Hysteresis (SU.HY)
Sub-SP (SP+SUB)
Main setting=Reverse and Sub-setting=Reverse
OFF
ON
Output
PV
Main SP (SP)
Hysteresis (HYS)
Hysteresis (SU.HY)
Sub-SP (SP+SUB)
8.2 Setting Control Type (CNT)
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...