9-5
IM 05P01D31-01EN
Auxiliary Control Functions
9
9.4 Forcing SP to Track Remote Input (SP Tracking)
Description
SP tracking function is the function to force the local setpoint (SP) to track the remote
setpoint (RSP) when the operation mode is switched from REM (remote) to LCL (local)
mode.
The function is effective to prevent abrupt PV changes.
REM → LCL mode switch
Time
REM → LCL mode switch
Time
SP tracking enabled
SP tracking disabled
PV
PV
SP
RSP
SP
RSP
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
SPT
SP tracking selection
STD
OFF, ON
SPS
Displayed only in cases where the communication is specified.