8-19
IM 05P01D31-01EN
Control Functions
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
CNT
Control type
EASY
PID: PID control
ONOF: ON/OFF control (1 point of
hysteresis)
ONOF2: ON/OFF control (2 points
of hysteresis)
2P2L: Two-position two-level
control
H/C: Heating/cooling control
CTL
HYS
Hysteresis
(in ON/OFF
control, Position
proportional
control, or Two-
position two-level
control)
Heating-side
ON/OFF control
hysteresis (in
Heating/cooling
control)
EASY
In ON/OFF control or Two-position
two-level control: 0.0 to 100.0% of
PV input range span (EUS)
In Heating/cooling control or
Position proportional control: 0.0
to 100.0%
PID
HYSc
Cooling-side
ON/OFF control
hysteresis
EASY
0.0 to 100.0%
DB
Output dead band
(in Heating/cooling
control or Position
proportional
control)
EASY
In Heating/cooling control: -100.0
to 50.0%
In Position proportional control: 1.0
to 10.0%
PIDN
PID number
selection
EASY
1 to 4
SP
PIDG.
Number of PID
groups
STD
1 to 4
CTL
Note1: The PID number (1 to 4, or R) is displayed on Group display while the parameter HYS,
HYSc, or DB is displayed.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
8
8.2 Setting Control Type (CNT)
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...