9.3 Forcing SP to Track PV (PV Tracking)
Description
PV tracking function is used to prevent abrupt PV changes.
With PV tracking, SP is first aligned with PV and then changed to its original SP at the
SP ramp rate.
► SP ramp-rate setting function: 9.2 Changing SP at a Fixed Rate (SP Ramp-Rate Setting
Function)
PV tracking function works when:
(1) Power is turned on or has recovered from a failure,
(2) SP number (SPNO) is changed,
(3) Operation mode is switched from STOP to RUN,
(4) Operation mode is switched from MAN to AUTO
PV tracking enabled
MAN
AUTO
MAN
AUTO
PV tracking disabled
PV
SP
PV
SP
Time
Time
Mode switch
Mode switch
Follows SP ramp rate
(set using UPR or DNR)
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
PVT
PV tracking selection
STD
OFF, ON
SPS