8-17
IM 05P01D31-01EN
Control Functions
8
When the Heating Side is in PID Control and the Cooling Side is in ON/OFF Control:
The following shows the formula and operation example.
HOUT = ( OUT
–
–
50% ) × 2
2
DB
*: OUT: control output, HOUT: heating-side control output,
COUT: cooling-side control output, DB: dead band, and
HYSc: cooling-side hysteresis
COUT = OUT < ( 50%
–
–
)
OUT > ( 50% + + )
Other than these cases, maintain current state.
Output turns on when
Output turns off when
2
DB
2
HYSc
2
DB
2
HYSc
Positive Dead Band
0%
Dead band
(DB)
Dead band
(DB)
Cooling-side control output (%)
Heating-side control output (%)
0%
50%
Control computation output
100%
100%
Heating-side
control output
high limit
(OH)
0%
100%
0%
50%
100%
Hysteresis (HYSc)
(OUT)
Negative Dead Band
0%
0%
50%
100%
100%
0%
100%
0%
50%
100%
Dead band
(DB)
Dead band
(DB)
Cooling-side control output (%)
Heating-side control output (%)
Control computation output
Heating-side
control output
high limit
(OH)
Hysteresis (HYSc)
(OUT)
8.2 Setting Control Type (CNT)
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...