H3 Analog Inputs
Selects the type of voltage signal input at terminal 16.
The resolution of terminal 16 is 11 bit.
The following table lists the function selections for the multi-function analog inputs (terminals 14 and
16), and indicates the control modes during which each function can be enabled.
H3-04 Terminal 16 Signal Selection
Terminal 16 Sel
B
B
B
B
Setting
Description
0
0 to 10V input (factory default)
1
-10 to +10V input
H3-05 Terminal 16 Multi-function Selection
Terminal 16 Sel
B
B
B
B
Setting
Function
Control Method (A1-02)
Setting Level
V/f
V/f w/ PG
Open Loop
Vector
Flux
Vector
0
Aux. Frequency Ref. (factory default)
√
√
√
√
±100% / ±10V
1
Frequency Gain
√
√
√
√
100% / 10V
2
Frequency Bias
√
√
√
√
±100% / ±10V
4
Voltage Bias
√
√
−
−
100% / 10V
5
Accel/Decel Change
√
√
√
√
100% / 1V
6
DC Injection Braking Current
√
√
√
−
100% / 10V
7
Overtorque Level
√
√
√
√
100% / 10V
8
Stall Prevention Level
√
√
−
−
100% / 10V
9
Reference Lower Limit
√
√
√
√
100% / 10V
A
Jump Frequency
√
√
√
√
100% / 10V
B
PID Feedback
√
√
√
√
±100% / ±10V
C
PID Reference Bias
<1110>
√
√
√
√
10V/Fmax
D
Frequency Reference Bias 2
<1110>
√
√
√
√
10V/Fmax
10
Forward Torque Limit
−
−
√
√
100% / ±10V
11
Reverse Torque Limit
−
−
√
√
100% / ±10V
12
Regenerative Torque Limit
−
−
√
√
100% / ±10V
13
Torque Reference
−
−
−
√
±100% / ±10V
14
Torque Compensation
−
−
−
√
±100% / ±10V
15
Forward/Reverse Torque Limit
−
−
√
√
±100% / 10V
1F
Not Used
−
−
−
−
−