VS-616G5 Programming Manual
95
H3
Analog Inputs
The VS-616G5 has three analog inputs (two multi-function and one reference), for the external input
of numerous references and limits, including frequency, torque, PID, and others. This section includes
descriptions of these functions.
Selects the type of voltage signal input at terminal 13.
The resolution of terminal 13 is 11 bit.
Setting Range:
0.0 to 1000.0%
Factory Default: 100.0%
Sets the terminal 13 input gain level when the reference voltage is 10V.
Setting Range:
-100.0 to 100.0%
Factory Default: 0.0%
Sets the terminal 13 input bias level when the reference voltage is 0V.
H3-01 Terminal 13 Signal Selection
Term 13 Signal
B
B
B
B
Setting
Description
0
0 to 10V input (factory default)
1
-10 to +10V input
H3-02 Terminal 13 Reference % Gain
Terminal 13 Gain
B
B
B
B
H3-03 Terminal 13 Reference ±% Bias
Terminal 13 Bias
B
B
B
B
Figure 46 Analog Input Gain and Bias Adjustment
+100
-100
0
Bias (%)
100
Reference (%)
1000
Gain (%)
Section H: Control Circuit Terminals
H3 Analog Inputs