VS-616G5 Programming Manual
123
Parameters set by user can be stored in the inverter as user default values.
Setting Range:
23P7 to 2075, 43P7 to 4300
Factory Default:
Inverter model dependent
Sets the inverter capacity, according to model number. Control parameters with defaults specific to the
inverter capacity are set automatically (i.e. carrier frequency, motor data, etc.). This parameter does not
need changing, unless the control board is replaced.
Selects whether the ENTER key is used when the frequency reference is set by the digital operator.
The digital operator can simulate a motor operated potentiometer (M.O.P.) by setting this parameter.
O2-03 User-Defined Default Value Setting
User Defaults
B
B
B
B
Setting
Description
0
No change (factory default)
1
Sets user-specified values as defaults.
Each parameter’s set values are stored as user defaults. Even if
the values are changed after this parameter is set, user defaults
can be restored by setting A1-03 = “1110” (user initialization). Up to
50 changed values can be stored.
2
Clears user defaults.
O2-04 Inverter Model Selection
Inverter Model #
A
A
A
A
O2-05 Digital Operator M.O.P. Mode Selection
Operator M.O.P.
A
A
A
A
Setting
Description
0
The digital operator M.O.P. mode is disabled (factory default). The inverter accepts the fre-
quency reference command when the ENTER key is depressed.
1
The digital operator M.O.P. mode is enabled. The inverter accepts the frequency
reference command as soon as changes are made with the arrow keys, without the
ENTER key being depressed.
Section L: Operator Parameters
O2 Key Selections