VS-616G5 Programming Manual
63
V/f
V/f w/PG Open Loop
Vector
Flux
Vector
Sets the motor phase-to-phase resistance value in units of 0.01W.
The default setting varies depending on the inverter model setting (O2-04).
Sets the motor leakage inductance in units of 0.1%. The default setting varies depending on the
inverter model setting (O2-04).
F
Option Parameters
F1
PG Option Set-up
These parameters can be accessed during operation using a pulse generator (PG) for speed feedback.
When access level is BASIC (A1-03), the parameter is not displayed unless the option card is con-
nected.
Setting Range:
0 to 60000
Factory Default:
1024
Sets the number of PG pulses per motor revolution (pulses/rev).
Selects the stopping method when a disconnected PG is detected.
E5-05 Motor 2 Terminal Resistance
Term Resistance
A
A
A
A
E5-06 Motor 2 Leakage Inductance
Leak Inductance
A
−
A
A
F1-01 PG Pulses per Revolution
PG Pulses/Rev
−
Q
−
Q
F1-02 PG Disconnection Detection Stopping Method
PG Fdbk Loss Sel
−
B
−
B
Setting
Description
0
Ramp to stop - according to C1-02
1
Coast to stop (factory default)
2
Fast-stop according to C1-09
3
Alarm flashes, operation continues (this setting is disabled
during flux vector control)
Phase-to-Phase Resistance at
273 + (25ºC + insulation class temperature) / 2
273 + insulation class temperature
Motor Terminal Resistance = Insulation Class Temperature ×
Section F: Option Parameters
F1 PG Option Set-up