130
VS-616G5 Programming Manual
Appendix
VS-616G5 Parameter List B Application
G
ro
up
b
A
pp
lic
at
io
n
PI
D
C
on
tro
l
B5-12
<1110>
PID Feedback Ref-
erence Missing
Detection Selection
(Fb Los Det Sel)
0~2
1
0
0: PID feedback missing
detection disabled. (Dis-
abled)
1: PID feedback missing
detection enabled. (Alarm)
Operation continues after
detection, “Fbl” alarm is dis-
played.
2: PID feedback missing
detection enabled. (Fault)
Inverter output is shut off
after detection, “Fbl” is dis-
played.
x
A
A
A
A
B5-13
<1110>
PID Feedback Ref-
erence Missing
Detection Level
(Fb los Det Lvl)
0~100
1%
0
—
x
A
A
A
A
B5-14
<1110>
PID Feedback Ref-
erence Missing
Detection Time
(Fb los Det Time)
0.0~
25.5
0.1s
1.0
—
x
A
A
A
A
Fu
nc
tio
n
b6
R
ef
er
en
ce
H
ol
d
B6-01
Dwell Frequency at
Start
(Dwell Ref @Start)
0.0~
400.0
0.1Hz
0.0
—
x
A
A
A
A
B6-02
Dwell Time at Start
(Dwell Time @
Start)
0.0~
10.0
0.1s
0.0
—
x
A
A
A
A
B6-03
Dwell Frequency at
Stop
(Dwell Ref @ Stop)
0.0~
400.0
0.1Hz
0.0
—
x
A
A
A
A
B6-04
Dwell Time at Stop
(Dwell Time @
Stop)
0.0~
10.0
0.1s
0.0
—
x
A
A
A
A
Fu
nc
tio
n
b7
D
ro
op
C
on
tro
l
D
ro
op
C
on
tro
l
B7-01
Droop Control Gain
(Droop Quantity)
0.0~
100.0
0.1%
0.0
—
o
-
-
-
A
B7-02
Droop Control
Delay Time
(Droop Delay Time)
0.03~
2.00
0.01s
0.05
—
o
-
-
-
A
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector