VS-616G5 Programming Manual
13
V/f
V/f w/PG Open Loop
Vector
Flux
Vector
· Coast to Stop (B1-03 = “1”)
Upon removal of the FWD (REV) run command, the motor starts to coast. After a stop command is
given, a run command is accepted and operation will start after the minimum baseblock time (L2-03)
elapses. If there is a possibility that a run command might be entered before the motor has come to a
stop, the speed search function (B3) or Coast to Stop with Timer 1 (B1-03 = “3”) should be employed.
· DC Injection Braking to Stop (B1-03 = “2”)
Upon removal of the FWD (REV) run command, the motor brakes to stop, according to the DC injec-
tion braking time at stop set in B2-04. If this value is set to “0” (factory default), DC injection braking
is disabled, and the motor coasts to stop. When choosing this function, note that the actual stop time is
the time set in B2-04 multiplied by 10 (see Figure 3 above). This stopping method is disabled during
flux vector control. Braking duty cycle should allow excess motor heat to dissipate.
Run command
ON
OFF
Output frequency
Inverter output is shut OFF
when stop command is given.
Figure 2 Stopping Method - Coast to Stop
Output Frequency
Run Command
ON
OFF
DC injection Braking Time
at Stop (B2-04)
Factory Default: 0.0s
Minimum Baseblock Time (L2-03)
Factory Default: 0.5s
Inverter Output OFF during
Figure 3 Stopping Method - DC Injection Braking to Stop
DC injection Braking Time
at Stop (B2-04)
DC injection
Braking Time
B2-04 x 10
Section B: Application Parameters
B1 Sequence