94
VS-616G5 Programming Manual
Section H: Control Circuit Terminals
H2 Digital Outputs
· Overtorque Detection 1 - N.C. (setting: “17”)
Closes during overtorque detection 1 (see section L6, Overtorque Detection, on page 113).
· Overtorque Detection 2 - N.O. (setting: “18”)
Closes during overtorque detection 2 (see section L6, Overtorque Detection, on page 113).
· Overtorque Detection 2 - N.C. (setting: “19”)
Opens during overtorque detection 2 (see section L6, Overtorque Detection, on page 113).
· During Reverse Run (setting: “1A”)
Closes during a reverse run command.
· Baseblock 2 - N.C. (setting: “1B”)
Opens when the inverter output shuts OFF.
· Motor 2 Selection (setting: “1C”)
Closed when motor 2 is selected.
Motor 2 may be selected by using a multi-function digital input.
· Motoring/Regenerating Mode (setting: “1D”)
Closes during regenerative operation (flux vector control only).
· Automatic Restart (setting: “1E”)
Closes during automatic restart operation.
· OL1 Pre-alarm (setting: “1F”)
Closes when the motor-calculated electronic thermal overload value increases to 90% of the internal
fault detection level.
· OH Pre-alarm (setting: “20”)
Closes when the heatsink temperature exceeds the overheat temperature level (L8-02), or when a
multi-function contact input (H1-__ = “B”) closes.
· Current/Torque Limit (setting: “30”)
Closes during torque limit.
· Speed Limit (setting: “31”)
Closes when the speed limit level (D5-03) is reached during torque control (flux vector control).
· Zero-Servo Completion (setting: “33”)
Closes when zero-servo operation is completed.
· During Run 2 (setting: “37”)
Closes when a run command is input (does not close during baseblock, injection braking or initial
excitation).