VS-616G5 Programming Manual
157
2. Monitor Display (Un-XX)
Fu
nc
tio
n
Parameter
No.
Name
(Digital Operator Display)
Min.
Unit
Description
Analog
Monitor
Output Level
Parameter Access Level
V/f
V/f w/
PG
Vector
w/o
PG
Vector
w/ PG
M
on
ito
r
U1-01
Frequency Reference
(Frequency Ref)
0.01Hz The unit differs depending on O1-03 setting.
10V/Max.
output
frequency
Q
Q
Q
Q
U1-02
Output Frequency
(Output Freq)
0.01Hz The unit differs depending on O1-03 setting.
10V/Max.
output
frequency
Q
Q
Q
Q
U1-03
Output Current
(Output Current)
0.1A
Minimum unit is 0.01 A for 7.5 kW or less.
10V/Inverter
rated
current
Q
Q
Q
Q
U1-04
Control Method*
(Control Method)
—
0: V/f control
1: V/f control with PG
2: Vector control without PG
3: Vector control with PG
—
Q
Q
Q
Q
U1-05
Motor Speed
(Motor Speed)
0.01Hz The unit differs depending on O1-03 setting.
10V/Max.
output fre-
quency
x
Q
Q
Q
U1-06
Output Voltage
(Output Voltage)
0.1V
—
10V/200V or
400V
?575
Q
Q
Q
Q
U1-07
DC Bus Voltage V
(DC Bus Voltage)
1V
—
10V/400V or
800V
Q
Q
Q
Q
M
on
ito
r
U1-08
Output Power
(Output kWatts)
0.1kW
—
10V/Inverter
capacity
(kW)
Q
Q
Q
Q
U1-09
Torque Reference
(Torque Reference)
0.1%
—
10V/Motor
rated torque
x
x
Q
Q
U1-10
Input Terminal Status*
(Input Term Sts)
—
—
Q
Q
Q
Q
U1-11
Output Terminal Status*
(Output Term Sts)
—
—
Q
Q
Q
Q
0
1: T1 “Closed”
1: T2 “Closed”
1: T3 “Closed”
1: T4 “Closed”
1: T5 “Closed”
1: T6 “Closed”
1: T7 “Closed”
1: T8 “Closed”
0 0 0 0 0 0 0
1: T9~ 10 “Closed”
1: T25 “Closed”
1: T26 “Closed”
0: Not used
0: Not used
0: Not used
0: Not used
1: Fault
0 0 0 0 0 0 0 0
Appendix
VS-616G5 Parameter List U Monitor
* Cannot be changed by U1-04