VS-616G5 Programming Manual
· Coast to Stop with Timer 1 (B1-03 = “3 ”)
After a stop command is given, a run command is not accepted while the coast to stop timer elapses
(same as Decel 1). After the timer runs out, another run command must be given for the inverter to
begin acceleration. This stopping method is disabled during flux vector control.
A “reverse run disabled” setting does not allow a reverse run command from the control circuit termi-
nal or the digital operator. This setting is used in applications where a reverse run command is undesir-
able.
B1-04 Prohibition of Reverse Operation
Reverse Oper
B
B
B
B
Setting
Description
0
Reverse run enabled (factory default)
1
Reverse run disabled
Output Frequency
Coasting
Decel Time 1
(C1-02)
Accel Time 1
(C1-01)
Time
ON
ON
ON
FWD (REV)
Run Command
Run Command Disabled
Figure 4 Stopping Method - Coast to Stop w/ Timer
Section B: Application Parameters
B1 Sequence