VS-616G5 Programming Manual
71
V/f
V/f w/PG Open Loop
Vector
Flux
Vector
F5
DO-02 Set-up
The DO-02C option card has 2 form C type dry contacts. Each of the dry contacts can be individually
set by F5-01 and F5-02.
The DO-02C option card connects to the control board at 3CN.
The table is a list of items that can be selected.
Selects the multi-function output selections for channel 1 of the DO-02C option.
For detailed information on these settings, refer to section H2, Digital Outputs, on page 88.
Setting Range:
Same as F5-01
Factory Default:
Zero speed (setting = “1”)
Selects the multi-function output selections for channel 2 of the DO-02C option.
F5-01 DO-02C Digital Output Channel 1 Selection
DO-02 CH1 Select
A
A
A
A
Setting
Description
Setting
Description
0
During run 1 (factory default)
13
Fref/Fout agree 2
1
Zero speed
14
Fref/set agree 2
2
Fref/Fout agree 1
15
Frequency detection 3
3
Fref/set agree 1
16
Frequency detection 4
4
Frequency detection 1
17
Torque detection 1 (N.C.)
5
Frequency detection 2
18
Torque detection 2 (N.O.)
6
Inverter ready
19
Torque detection 2 (N.C.)
7
DC bus undervoltage
1A
Reverse direction
8
Baseblock 1
1B
Baseblock 2
9
Option frequency reference
1C
Motor 2 selected
A
Remote operation
1D
Regenerating
B
Torque detection 1 (N.O.)
1E
Restart enabled
C
Loss of reference
1F
Overload (OL1)
D
DB overheat
20
OH pre-alarm
E
Fault
30
Current/torque limit
F
Not used
31
Speed limit
10
Minor fault
33
Zero servo end
11
Reset command active
37
During run 2
12
Timer output
-
--
F5-02 DO-02C Digital Output Channel 2 Selection
DO-02 CH2 Select
A
A
A
A
Section F: Option Parameters
F5 DO-02
Option Set-up