V/f
V/f w/PG Open Loop
Vector
Flux
Vector
64
VS-616G5 Programming Manual
Section F: Option Parameters
F1 PG Option Set-up
Selects the stopping method when an overspeed condition is detected.
Selects the stopping method when excessive speed deviation is detected.
Sets the relationship between the motor rotation direction and PG polarity.
The motor rotation direction applies when viewing the motor shaft from the load side.
Setting Range:
1 to 132
Factory Default:
1
Sets the division ratio for monitoring the PG pulse signals.
F1-03 Overspeed Detection Stopping Method
PG Overspeed Sel
−
B
−
B
Setting
Description
0
Ramp to stop - according to C1-02
1
Coast to stop (factory default)
2
Fast-stop according to C1-09
3
Alarm flashes, operation continues (this setting is disabled
during flux vector control)
F1-04 PG Deviation Detection Stopping Method
PG Deviation Sel
−
B
−
B
Setting
Description
0
Ramp to stop - according to C1-02
1
Coast to stop
2
Fast-stop according to C1-09
3
Alarm flashes, operation continues (factory default)
F1-05 PG Rotation Selection
PG Rotation Sel
−
B
−
B
Setting
Description
0
Motor FWD direction is counterclockwise (factory default).
1
Motor FWD direction is clockwise.
F1-06 PG Division Rate (pulse output)
PG Output Ratio
−
B
−
B