VS-616G5 Programming Manual
47
V/f
V/f w/PG Open Loop
Vector
Flux
Vector
D2
Reference Limits
Setting Range:
0.0 to 110.0%
Factory Default:
100.0%
The frequency reference upper limit is set as a percentage of the maximum output frequency (E1-04)
in increments of 1%.
Setting Range:
0.0 to 109.0%
Factory Default:
100.0%
The frequency reference lower limit is set as a percentage of the maximum output frequency (E1-04)
in increments of 1%. When a run command is input and the frequency reference is less than the lower
limit, operation continues at the frequency reference lower limit. However, when the lower limit is set
to less than the minimum output frequency (E1-09), operation discontinues.
D3
Jump Frequencies
This function allows the prohibition or “jumping” of critical frequencies so that the motor can operate
without resonant vibrations caused by some machine systems. This function is also used for dead-band
control. Setting the value to 0.0Hz disables this function.
D2-01 Frequency Reference Upper Limit
Ref Upper Limit
B
B
B
B
D2-02 Frequency Reference Lower Limit
Ref Lower Limit
B
B
B
B
D3-01 Jump Frequency Reference 1
Jump Freq 1
B
B
B
B
D3-02 Jump Frequency Reference 2
Jump Freq 2
B
B
B
B
D3-03 Jump Frequency Reference 3
Jump Freq 3
B
B
B
B
D3-04 Jump Frequency Reference Bandwidth
Jump Bandwidth
B
B
B
B
D2-01
Set Frequency Reference
Internal
Frequency
Reference
D2-02
Figure 25 Setting Frequency Upper and Lower Limits
100
0
E1-04
%
Hz
Section D: Reference Parameters
D2 Reference Limit / D3 Jump Frequency