104
VS-616G5 Programming Manual
Section L: Protection Parameters
L2 Power Loss Ridethrough
Setting Range:
0.0 to 2.0s
Factory Default:
Inverter model dependent
Sets the ridethrough time allowed before the inverter trips, after momentary power loss. This setting is
activated when L2-01 is set to “1”. If power is restored within this time, operation restarts automati-
cally. If power is not restored within this time, a fault contact trips, stopping the inverter.
2
Momentary power loss ridethrough is enabled, within the control
logic time, regardless of the time set in L2-02. The control logic
time differs depending on inverter capacity.
L2-02
Momentary Power Loss Ridethrough Time
PwrL RideThru t
B
B
B
B
Setting
Description