VS-616G5 Programming Manual
121
Selects the monitor to be displayed on the digital operator immediately after the power supply is turned
ON.
Units for parameters and monitors related to frequency can be scaled as shown below.
O1-02 Monitor Selection After Power-up
Power-On Monitor
B
B
B
B
Setting
Description
1
Displays frequency reference (factory default).
2
Displays output frequency.
3
Displays output current.
4
Displays the monitor set in O1-01.
O1-03 Scale for Setting and Monitoring Frequency
Display Scaling
B
B
B
B
Setting
Description
00000
Unit: 0.01Hz (factory default)
00001
Unit: 0.01%
00002 to 00039
Unit: rpm (0 to 3999)
00040 to 03999
(user-selected units)
Digits:
5th
4th
3rd
2nd
1st
0
0
0
0
0
The 1st thru 4th digits determine the set value at 100% output frequency.
Decimal point position is set by the 5th digit as follows:
5th digit = 0: displayed as 0000
5th digit = 1: displayed as 000.0
5th digit = 2: displayed as 00.00
5th digit = 3: displayed as 0.000
Example 1
If 100% output frequency is equal to 200.0 units:
Set O1-03 = “12000”; 100% of this reference is displayed as 200.0 and 60%
of this reference is displayed as 120.0.
Example 2
If 100% output frequency is equal to 65.00:
Set O1-03 = “26500”; 60% of this reference is displayed as 39.00.
Section L: Operator Parameters
O1 Monitor Selection