Section L: Protection Parameters
L8 Hardware Protection
L8
Hardware Protection
The VS-616-G5 comes equipped with a number of built-in functions designed to protect the inverter
and its components from damage. This section describes the set-up of these functions.
When a Yaskawa dynamic braking resistor is used, protection against overheat is enabled with this func-
tion. The duty cycle of the braking resistor is monitored in software so that it does not exceed 3%.
If the duty cycle exceeds 3%, a DB overheat fault (RH) occurs, and the inverter coasts to stop.
Setting Range:
0 to 100
°
C
Factory Default:
100
°
C
Sets the heatsink temperature level for protection against overheat (OH).
L8-01
Protection Selection for Internal DB Resistor
DB Resistor Prot
B
B
B
B
Setting
Description
0
DB resistor overheat protection is not provided (factory default).
1
DB resistor overheat protection is provided.
L8-02
OH Pre-Alarm Level
OH Pre-Alarm Lvl
A
A
A
A
0
REV Run Regen
Torque Limit (L7-04)
Positive Torque Reference
Negative Torque Reference
FWD Motor Rotation
REV Motor Rotation
REV Run Motor
Torque Limit (L7-02)
FWD Run Regen
Torque Limit (L7-03)
FWD Run Motor
Torque Limit (L7-04)
Figure 56 Torque Limit - 4 Quadrant Operation