16.2 Alarm Displays
16.2.6 Resetting Alarms Detected in Option Modules
16-45
16
Maintenance
16.2.6
Resetting Alarms Detected in Option Modules
If any Option Modules are attached to the SERVOPACK, the SERVOPACK detects the pres-
ence and models of the connected Option Modules. If it finds any errors, it outputs alarms.
You can delete those alarms with this operation.
Preparations
Always check the following before you clear an alarm detected in an Option Module.
•
The parameters must not be write prohibited.
Applicable Tools
The following table lists the tools that you can use to reset Option Module configuration errors
and the applicable tool functions.
Operating Procedure
Use the following procedure to reset alarms detected in Option Modules.
1.
Click the
Servo Drive Button in the workspace of the Main Window of the Sig-
maWin+.
2.
Select
Reset Option Module Configuration Error
in the Menu Dialog Box.
The Reset Option Module Configuration Error Dialog Box will be displayed.
3.
Select the
Clear
Check Box for the Option Modules from which to clear alarms and the
click the
Execute
Button.
•
This operation is the only way to reset alarms for Option Modules. The alarms are not reset
when you reset other alarms or when you turn OFF the power supply to the SERVOPACK.
•
Always remove the cause of an alarm before you reset the alarm.