9-39
15964
5-1CD
RE-CHO-A1
11
FS
10
0
16
RExG parameter error
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate parameter file in
maintenance mode, and then load the parameter file saved in the external
memory device.
Main CPU board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
1031
MEMORY ERROR
(MOTION1)
0
"GET FILE" instruction, "SET
FILE" instruction execution target
file
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
1
Home position calibration file
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
2
Tool file
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
3
User coordinates file
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
4
Robot calibration file
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
5
Tool calibration file
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
7
Home position correction data file
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
8
Conveyor calibration file
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
9
Arm and tool interference
prevention file
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
34
Conveyor condition file
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy
141 of 348