9-162
1596
45-1
C
D
RE-CHO-A1
11
FS10
0
8
Among three points in the slave-
group's calibration data, two or
three points are on the same
point.
Setting error
(1)Check the following settings.
·Teach the data for calibration so that each point is different.
9
The number of the teaching points
for calibration data is insufficient.
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
4469
ROBOT CALIBRATION
FRAME ERROR
1
The calibration between
manipulators cannot be executed
for this model.
Setting error
(1)Check the following settings.
·The calibration function between manipulators cannot be used for this model.
2
The master group and the slave
group are set to the same group.
Setting error
(1)Check the following settings.
·Set the different groups for the master group and the slave group.
3
Incorrect designation of the
control group for master group
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
4
Incorrect designation of the
control group for slave group
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
5
Calibration data setting error
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
4470
ROBOT CARIB STEP
NOT ENOUGH
Setting error
(1)Check the following settings.
·Check the settings for number of the job steps
4471
ROBOT CALIBRATION
DATA ERROR
1
Incorrect number of teaching
points for tool calibration
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
2
Incorrect designation of the
occupation control group for
calibration data
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy
264 of 348