An error occurred in the creation
of transmission socket during the
UDP process of the Ethernet
function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
Main CPU board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
3
Illegal data were received in the
UDP process of the Ethernet
function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
Main CPU board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
4
Transmission error occurred in the
UDP process of the Ethernet
function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
Main CPU board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
5
The SELECT operation was not
successfully completed in the
UDP process of the Ethernet
function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
Main CPU board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
100
The re-initialization notification of
illegal data length was received in
the UDP process of the Ethernet
function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
Main CPU board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
101
The re-initialization notification of
illegal data was received in the
UDP process of the Ethernet
function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
Main CPU board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.