9-100
1596
45-1
C
D
RE-CHO-A1
11
FS10
0
6
Unused position data file is
destroyed.
Software operation error
occurred
(1)Reset the alarm.
(2)If the error occurs again, delete the job where the alarm occurred.
(3)If the error occurs again after the previous measures were executed,
initialize the job file in the maintenance mode, and then load the saved job file.
(4)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
7
Unused position data file does not
exist.
Setting error
(1)Check the following settings.
·The number of steps in job (position data)
Delete unnecessary position data in job and add new position data.
Software operation error
occurred
(1)Reset the alarm.
(2)If the error occurs again, delete the job where the alarm occurred.
(3)If the error occurs again after the previous measures were executed,
initialize the job file in the maintenance mode, and then load the saved job file.
(4)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
8
Position data file is destroyed.
Software operation error
occurred
(1)Reset the alarm.
(2)If the error occurs again, delete the job where the alarm occurred.
(3)If the error occurs again after the previous measures were executed,
initialize the job file in the maintenance mode, and then load the saved job file.
(4)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
9
Position data control information
is destroyed.
Software operation error
occurred
(1)Reset the alarm.
(2)If the error occurs again, delete the job where the alarm occurred.
(3)If the error occurs again after the previous measures were executed,
initialize the job file in the maintenance mode, and then load the saved job file.
(4)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
10
An error occurred in specified
position data number.
Software operation error
occurred
(1)Reset the alarm.
(2)If the error occurs again, delete the job where the alarm occurred.
(3)If the error occurs again after the previous measures were executed,
initialize the job file in the maintenance mode, and then load the saved job file.
(4)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy
202 of 348