15.2 Alarm Displays
15.2.7 Resetting Alarms Detected in Option Modules
15-51
15
Maintenance
Operating Procedure
Use the following procedure to reset alarms detected in Option Modules.
1.
Click the
Servo Drive Button in the workspace of the Main Window of the Sig-
maWin+.
2.
Select
Reset Option Module Configuration Error
in the Menu Dialog Box.
The Reset Option Module Configuration Error Dialog Box will be displayed.
3.
Select the
Clear
Check Box for the Option Modules from which to clear alarms and the
click the
Execute
Button.
4.
Click the
OK
Button.
5.
Click the
OK
Button.
6.
Turn the power supply to the SERVOPACK OFF and ON again.
This concludes the procedure to reset alarms detected in Option Modules.