15.2 Alarm Displays
15.2.3 INDEXER Module Alarm Displays and Troubleshooting
15-46
E1BA
A.AEF
Program Out-of-
range Alarm
(Detected only
when control
power supply is
turned ON.)
A value set in the pro-
gram table is not
within the allowed
setting range.
•
Change the firmware
version.
•
Change the program
table version to
match the firmware
version.
Gr.1
Available
*1
E1CA
A.AEF
ZONE Table
Checksum Alarm
(Detected only
when control
power supply is
turned ON.)
The ZONE table
stored in flash mem-
ory was not recorded
properly.
(This alarm can occur
if the control power
supply is turned OFF
while the ZONE table
is being saved or ini-
tialized.)
•
Initialize the ZONE
table with the
ZONEINIT command
or FnB07.
*2
•
If the problem is not
solved, correct the
ZONE table.
Gr.1
Available
*2
E1DA
A.AEF
ZONE Table Ver-
sion Unmatched
(Detected only
when the control
power supply is
turned ON.)
The combination of
the firmware version
and the ZONE table
version is wrong.
•
Change the firmware
version.
•
Change the ZONE
table version to
match the firmware
version.
Gr.1
Available
*2
E1EA
A.AEF
ZONE Table Out-
of-range Alarm
(Detected only
when control
power supply is
turned ON.)
A value set in the
ZONE table is not
within the allowed
setting range.
•
Change the firmware
version.
•
Change the ZONE
table version to
match the firmware
version.
Gr.1
Available
*2
E1FA
A.AEF
JOG Speed
Table Checksum
Alarm
(Detected only
when control
power supply is
turned ON.)
The JOG speed table
stored in flash mem-
ory was not recorded
properly.
(This alarm can occur
if the control power
supply is turned OFF
while the JOG speed
table is being saved
or initialized.)
•
Initialize the JOG
speed table with the
JSPDINIT command
or FnB08.
•
If the problem is not
solved, correct the
JOG speed table.
Gr.1
Available
*3
E21A
A.AEF
JOG Speed
Table Version
Unmatched
(Detected only
when the control
power supply is
turned ON.)
The combination of
the firmware version
and the JOG speed
table version is
wrong.
•
Change the firmware
version.
•
Change the JOG
speed table version
to match the firm-
ware version.
Gr.1
Available
*3
E22A
A.AEF
JOG Speed
Table Out-of-
range Alarm
(Detected only
when control
power supply is
turned ON.)
A value set in the
JOG speed table is
not within the allowed
setting range.
•
Change the firmware
version.
•
Change the JOG
speed table version
to match the firm-
ware version.
Gr.1
Available
*3
Continued on next page.
Continued from previous page.
Serial
Command
Negative
Response
Alarm
Number
Alarm Name
Meaning
Corrective Action
Servo-
motor
Stop
Method
Alarm
Reset